banner
News center
Our products are effortless, handy, and safe to use.

Using Control Valve Installed Gain Calculations

Sep 30, 2023

A worksheet that calculates control valve installed gain can be part of any control valve selection process. This article was originally published in the December 2021 issue of InTech magazine.

For many years, the author has used, and promoted the use of, control valve installed flow and gain graphs as part of the control valve selection process (references 1–3). For all those years, the author has had the benefit of being associated with a valve manufacturer with a publicly available control valve-sizing application that included installed flow and gain graphing capability. Users who preferred other brands of control valves, and thus those manufacturers’ control valve-sizing applications, were hesitant to learn to use a new application to take advantage of the graphing capability.Recently, the author published an article that included detailed instructions for constructing a Microsoft Excel worksheet that generates installed flow and gain graphs in conjunction with valve-sizing calculations made with any valve-sizing application. This makes it practical for anyone to incorporate graphing installed flow and gain into their valve selection process (reference 4). This article explains how to use control valve installed gain calculations.

Extremely low gains are undesirable, because a low gain means when the valve moves, the flow does not change by much. It might not be as obvious why high gains are undesirable. An audio amplifier with a high gain may be desirable. But control valves are mechanical devices, and parts that move while in contact with each other tend to stick when not moving. If a valve, because it tends to stick when not moving, can only be positioned within 2% of the desired position and has a gain of 4, the flow can only be adjusted within 8% steps, which may not be desirable. The reason for limiting the gain change within the required flow range to 2:1 is so it will be easier to tune the controller for stable and fast response throughout the required flow range.To calculate and graph the installed flow and gain using the reference 4 worksheet, the process model and the worksheet require the following information about the process:

The values of P1 and P2 at the minimum and maximum design flow need to be obtained by an analysis of the frictional pressure losses and static pressure changes in the system upstream and downstream of the control valve (references 5–6).Reference 4 prompted several inquiries as to what applications would be candidates for installed flow and gain graph analysis. Below are some of the most common.

Figure 2 shows a user's Excel control valve-sizing worksheet. The calculated CV range appears to show a 6-inch segment ball control valve would be operating at about 20% to 78% open from the minimum design flow to the maximum design flow. An installed flow and gain calculation yielded surprising results (Figure 3).

The installed flow graph shows the minimum specified flow intersecting the installed flow graph at 20% relative travel, and the maximum design flow intersecting the installed flow graph just a bit below 80% relative travel, which agrees with the user's calculation. What the user's calculation did not show is 95% of the valve's fully open flow is at the maximum design flow, leaving no safety factor at the high end.At about 60% travel (relative travel of 0.6), the installed flow graph starts rounding off to a much shallower slope. This fact is identified on the installed gain graph where the installed gain drops to below 0.5, emphasizing the fact that changes in valve position would have only a small effect on flow in the system. The gain change from the maximum design flow (Q/Qmax) and the maximum gain on the graph is greater than 4:1, making it difficult to tune the controller for fast and stable control. It turned out the problem lies with the user's pump choice.

Reference 4 does not include the ability to graph what is happening to P1 and P2, and thus the pressure differential available to the valve. However, the reference 4 worksheet has a tabulation of P1 and P2, so constructing a graph of P1 and P2 versus relative valve travel was simple. In the installed pressure level graph, as valve relative travel approaches 0.8 (80% valve travel), the pressure drop available to the valve decreases rapidly.

The user found a pump with a slightly higher and flatter head curve. A new analysis of the upstream system gave the revised values of P1 and DELTA P shown in red in Figure 4. Putting these new values of P1 and DELTA P into the user's valve-sizing program and into the reference 4 worksheet gives the graphs of Figure 4. The valve is now operating between 25% and 75% travel. The maximum design flow is now at slightly less than 80% of the fully open flow, giving ample safety factor at the high end of the range. The installed gain graph is much flatter and well within the suggested limits.

Figure 5 is based on an application where the system designer recommended a 10-inch segment ball valve after examining the installed flow and gain graphs and determining the segment valve was a good choice. The purchasing agent commented that a 10-inch high-performance butterfly valve would cost approximately one-third less than the segment ball valve. The system designer agreed to investigate the applicability of a high-performance butterfly valve, knowing the two valve styles have quite different inherent flow characteristics. Segment ball valves tend to have a nearly perfect equal percentage characteristic. High-performance butterfly valves tend to have an inherent flow characteristic between linear and equal percentage.

A question arose regarding the pressure drop to use when sizing a control valve. Assuming a system that has already been designed, the sizing pressure cannot be arbitrarily assigned, but the values of P1 and P2 need to be obtained by an analysis of the frictional pressure losses and static pressure changes in the system both upstream and downstream of the control valve. The ideal situation is where the person selecting the control valve has a say in determining what the control valve pressure drop will be, most often by specifying the pump that will be used. Using an installed gain analysis of various pumps that might be suitable can be helpful.To demonstrate how this can be done, three possible pumps for the system shown in Figure 6 will be considered, and the one that allows satisfactory controllability while minimizing energy consumption will be selected. Curves of P1, the pressure just upstream of the valve, are shown for each of the three pumps, along with the power required by each at a normal flow rate of 400 gpm. These curves slope downward in proportion to the flow squared from the 100 gpm pump head (45, 60, and 75 psig, respectively, for pumps A, B, and C) to a pressure 10 psi lower due to the combined effect of the 5 psi pressure loss in the upstream piping and the 5 psi decrease in pump head from 100 gpm to 600 gpm stated in the figure. The curve for P2, the pressure at the control valve outlet, starts with the 10 psig static head of the tank at very low flows and increases in proportion to the flow squared to 30 psig as the downstream piping and heat exchanger pressure losses increase to their 600 gpm values.

The control valve pressure drops (the difference between P1 and P2) are indicated in the figure by the arrows at the left side of the figure for 100 gpm and at the right side of the figure for 600 gpm. The analysis is performed based on using a segment ball valve. The graph in the lower left of Figure 6 shows the calculated installed flow characteristics. Keep in mind the installed flow graphs generated by the worksheet of the reference 4 graph is relative flow, so 1.0 is 100% of the fully open flow, which is different for each of the three cases. What is interesting is the installed gain graphs.With the 17-hp pump, besides requiring a more expensive 6-inch valve, the gain graph looks terrible. The installed gain is the highest of the three (meaning a larger flow error for the same valve position error), it drops to 0.4 as it approaches the maximum design flow (the red vertical line at 1.0 on the Q/Qmax scale), and the variation in gain over the flow range is almost 7:1, much greater than the recommendation of 2:1. This is large enough that it would be difficult to come up with proportional-integral-derivative (PID) tuning parameters that would provide good and stable control over the entire required flow range. The gain graphs of the 23-hp and 29-hp pumps fall within the recommended gain criteria, but the 23-hp pump is the winner, because its gain is closer to 1.0, and it also is the more economical of the two to operate.References

1. Monsen, Jon, Rules of Thumb, Flow Control, November 2012 pp. 24–262. Monsen, Jon, An Insider's Guide to Installed Gain as a Control Valve Sizing Criterion, Flow Control, May 2015, pp. 22-25.3. Monsen, Jon, Modern Tools for Sizing Control Valves & Actuators, Processing, January 2018 pp. 12-144. Monsen, Jon, Calculating the Installed Flow and Gain of a Control Valve, Process Instrumentation, March 2021, pp. 26–30. (The worksheet described in the reference and an enhanced version are available.)5. Jessee, Peter, Determining Pressure Drop for Control Valve Sizing, Flow Control, August 2000, pp. 12-14.6. Coggan, D. A, ed., "Fundamentals of Industrial Control," Second Edition, Research Triangle Park, NC: Instrumentation, Systems, and Automation Society (ISA) (now the International Society of Automation—ISA), 2004. pp. 278–280.

This article was originally published in the December 2021 issue of InTech magazine.

Jon F. Monsen, PhD, PE, is a control valve technology consultant for Valin Corp., the author of the chapter on "Computerized Control Valve Sizing" in the ISA Practical Guides Book on Control Valves, and the author of the book Control Valve Application Technology: Techniques and Considerations for Properly Selecting the Right Control Valve. With his more than 40 years of experience, he has lectured nationally and internationally about control valve application and sizing, and he hosts a website where he offers free information and Excel worksheets for those who specify or use control valves.

Check out our free e-newsletters to read more great articles..